Friday, August 10, 2018

Register Sealing before having BECT do a duct leakage test


Subject : Register Sealing before having BECT do a duct leakage test

Hello,
Please make sure that the registers are sealed as in the photo below, before BECT comes to test the system for duct leakage.
Seal the register boxes to drywall or hardwood floor with UL 181 aluminum tape as shown below.

Aluminum Tape (must be UL 181)        

                              Register sealed to drywall with Al tape.


The photos below are examples of what the registers/returns should not look like.
Unsealed boot in drywall, on ceiling. This won't hold air.





Unsealed 1950s boot in hardwood floor, unsealed.




1920s register boot, unsealed to plaster yet painted black.

Also, please make sure that your forced air unit set on the highest speed so that you can achieve 350 cfm/ton​ for the 1. Total Airflow Test and 2. The Fan/Watt Draw Test.


Also, don't forget to drill a 1/4 inch hole in each side of the plenum (both supply plenum and return plenum) and mark the hole, HSSP, for Hole for Static Pressure Probe. Put aluminum tape over the hole but make sure marking is visible for HERS test. If those access holes are not there - you'll need to do it at the test. They are so that someone can insert a probe on each side and see the difference in temperature and humidity changes before and after the air moves through the evaporator coil.

If you have any questions on how to seal it, we also have a video on our website detailing how to properly seal your ducts. Click this link here to watch the video, http://bect.us/videos/. You can also watch our other videos on energy efficiency in the home on BECT's YouTube channel. Check it out here, https://www.youtube.com/channel/UCAd8LCb6fzHAkzqOu9loGrQ/videos?view_as=subscriber.



Stay cool and comfortable, 


BECT

Tuesday, January 5, 2016

Filter Grill Requirements Update from the CEC

While testing at BECT.us I have come across a number of air conditioning systems that do not meet the total airflow and fan/watt draw levels of performance that the code calls for. When this happen the HVAC contractor has to redo the return duct design and then install it at significant cost of time and reputation. It shows that the system was never actually designed but pieced together using a best guess. There has got to be a better way.

The CEC has just sent out an update of their filter grill requirements which are a critical part of the return duct system. Here is there update.

"Filter Grille Area Requirements
When complying with the Alternative to Section 150.0(m)13B, the nominal size of the air filter media should be used to calculate the minimum total return filter grille gross area. If the air filter is not located at the filter grille, use the nominal size of the filter grille to determine the area. The calculated area must be equal to or greater than the values in TABLES 150.0-C or D.
Additionally, TABLES 150.0-C and D also require that:

 1. Each return duct must be no longer than 30 feet.

2. Each return duct must not have more than 180 degrees of total bend.

3. If the total bending of a return duct is more than 90 degrees, one bend must be a metal elbow.

4. Return grille devices, which include the air filter and return grille locations, must be labeled in accordance with the requirements of Section 150.0(m)12A.


 5. The label must state the grille’s design airflow rate and a maximum allowable clean-filter pressure drop of 12.5 Pa (0.05 inches water) for the air filter, as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. Please note that additional air filtration requirements of Section 150.0(m)12 may apply."

I've seen some contractors who were shocked at how much filter area the code was calling for. Of course, the best way to make sure that the filter grill requirements are met is to use a proper duct design system such as Right Soft. The vast majority of installations that I see are not designed at all.

I hope that bringing this to light could alleviate some of the pain I've seen in the eyes of someone who has to redo their hard work often in a sweltering attic.